What is a thermostatic mixing valve (TMV)?

A thermostatic mixing valve (TMV) is a device that blends hot and cold water to deliver water at a safe, preset temperature, protecting users from scalding.

A thermostatic mixing valve automatically balances incoming hot and cold water supplies to maintain a steady outlet temperature, even when either line fluctuates. The valve contains a temperature-sensitive cartridge that responds to changes in water temperature and adjusts the mix in real time.

A thermostatic mixing valve is built to hold the outlet temperature steady and to protect against scalding when the hot or cold supply changes or shuts off. A tempering valve also mixes hot and cold water to a lower temperature, but in WA only a thermostatic mixing valve or a thermostatically controlled tap is permitted where the limit is 45°C.

In WA a thermostatic mixing valve or thermostatically controlled tap is required where hot water is limited to 45°C: the residential parts of aged care buildings, patient care areas in health care buildings, the parts of early childhood centres and schools used by children, and designated accessible facilities in some commercial and shared buildings. Ordinary home bathrooms are limited to 50°C and may use a tempering valve, a thermostatic mixing valve, a thermostatically controlled tap or a temperature-limited water heater.

A qualified plumber will size and set the valve according to site conditions and local compliance requirements. TMVs require periodic maintenance and cartridge replacement to remain effective, as internal components can wear or become blocked by mineral deposits.