What is a tempering valve?

A tempering valve is a mixing device installed on hot water systems that blends incoming hot water with cold supply water to deliver a preset safe temperature at the outlet.

A tempering valve reduces the risk of scalding by automatically mixing hot water from a storage tank or instantaneous system with incoming cold water. It maintains a steady, safe delivery temperature even as demand and source temperatures fluctuate. The valve opens and closes internal ports to balance the flow and regulate outlet temperature without requiring user adjustment at the tap.

In Western Australia the Plumbing Code of Australia sets the rule, and it is a limit on delivery temperature rather than a requirement for one particular valve. Hot water at fixtures used for personal hygiene, such as showers and baths, must not exceed 50°C, or 45°C in settings such as aged care and early childhood centres. The limit applies to a new hot water installation and when a water heater is replaced, relocated or added. At 50°C a tempering valve is one of the permitted devices, alongside a thermostatic mixing valve, a thermostatically controlled tap or a temperature-limited water heater. Water at 60°C can scald a child in about a second, which is why the limit exists.

A licensed plumber sizes and commissions the valve to match the property's system type and flow demand. The valve requires periodic testing and maintenance to ensure it continues operating at the correct temperature setpoint and responds reliably to changes in hot or cold supply pressure.